Kuggen. Ecopilot, energenious building automation system
Renovation
- Building Type : Office building < 28m
- Construction Year : 2011
- Delivery year : 2014
- Address 1 - street : 412 96 GOTHENBURG, Sweden
- Climate zone : [Dfc] Wet subarctic, cool summer, severe winter
- Net Floor Area : 4 898 m2
- Construction/refurbishment cost : 50 000 €
- Number of Work station : 1 Work station
- Cost/m2 : 10.21 €/m2
-
Primary energy need
37 kWhpe/m2.year
(Calculation method : Primary energy needs )
Kabona is a company which works with energenious energy building automation and the company’s head office is locatedin Borås, Sweden. Kabona was founded in 2001 and has long-standing and solidexperience, which has formed the basis of our innovative and energy smartproduct Ecopilot. Since 2012 Kabona has been owned by Investment AB Latourwhich is registered on the Stockholm Stock Exchange under Large Cap.
Project property Kuggen, Lindholmen Göteborg – independent evaluation of Ecopilot in amodern office building
The project’s aim is a thorough evaluation of special functions for integrated control of heating, cooling and ventilation, specifically adapted to utilise the building’s thermal inertia.Kabona refers to a long series of projects where Ecopilot has resulted inenergy savings of 25%, with retained or improved quality of the indoor climate. However, no independent evaluation of the system has been conducted yet, whichis the aim of this project.
About the building
The building Kuggen is an office building of 4,898 m2 divided on 5 floors and was put into operation in 2011. From the start, even before Ecopilot, the building had good energy performance and has been certified in accordance with the EU programme for energy-efficient building, Green Building.
Installation of the new superior control system, Ecopilot, was conducted on 27 August 2014 and this evaluation focused on how this has impacted the indoor environment, energy consumption and operation.
The building’s performance before Ecopilot
According to the energy statistics of 2013from Göteborg Energi, Kuggen’s energy consumption is 37 kWh/m2 peryear for heating (temperature corrected) and 9 kWh/m2 for districtcooling. In 2013 the consumption of property electricity amounted to 27 kWh/m2year and business electricity to 28 kWh/m2. The results of consumption before and after Ecopilot are presented under conclusion below.
Evaluation
The evaluation was performed by an independent party, CIT Energy Management AB, without links to the supplier of Ecopilot. In order to ensure correct installation and operation of the system,CIT collaborates with both Chalmersfastigheter and Kabona. This evaluationcovers six months (the time period September 2014 – February 2015).
See more details about this project
https://sv.wikipedia.org/wiki/Kuggenhttp://www.energi-miljo.se/artikelem/ny-styrning-viktig-kugge-for-miljon/
Stakeholders
Other consultancy agency
CIT Energy Management AB
Lars Ekberg; [email protected]
http://www.energy-management.seContracting method
Other methods
Energy consumption
- 37,00 kWhpe/m2.year
- 55,00 kWhpe/m2.year
- 73,00 kWhpe/m2.year
Envelope performance
- 1,00 W.m-2.K-1
More information
All kwh above was BEFORE we installed the Ecopilot.
Energy savings with Ecopilot:
Heating: -49%
Cooling: -50%
Property electricity: -30%
Real final energy consumption
42,00 kWhfe/m2.year
42,00 kWhfe/m2.year
2 013
Systems
- Urban network
- Heat pump
- Heat pump
- Solar Thermal
- Urban network
- VAV Syst. (Variable Air Volume system)
- Natural ventilation
- Free-cooling
- Solar Thermal
- No renewable energy systems
Smart Building
Urban environment
Product
Ecopilot

Kabona AB
Ulf Falkenby; [email protected]
http://www.ecopilot.com
Ecopilot is a new system with integrated control of ventilation, heating and cooling. Ecopilot functions brilliantly, both for new production and existing properties where we over-modulate existing BMS. The system particularly takes into account heat storage in the building and thereby counteracts the need of, in a short duration, alternating from heating to cooling, and vice versa. Ecopilot optmises energy with respect to internal loads, weather forcast, indoor temperature, wind impact and sun insolation.
They are very happy about the huge enrgy savings that we have accomplished
The conclusions which could be drawn are that the requirements for the indoor environment are fulfilled with Ecopilot and that with the new control you have greater variations in the room temperature and air flow, especially during the summer drop, but that the greater variation takes place outside the comfort periods.
There is a full report from this study that you can get from Mr Lars Ekberg at CIT Management
Construction and exploitation costs
- 40 000 €
- 8 000 €
Indoor Air quality
Reasons for participating in the competition(s)
This summery is for both categories:Kabona
AB
Kabona is a company which works with
brilliant energy building automation and the company’s head office is located
in Borås, Sweden. Kabona was founded in 2001 and has long-standing and solid
experience, which has formed the basis of our innovative and energy smart
product Ecopilot.
Our
unique product – Ecopilot
Ecopilot is a new system with integrated
control of ventilation, heating and cooling. Ecopilot functions brilliantly,
both for new production and existing properties where we over-modulate existing
equipment. The system particularly takes into account heat storage in the
building and thereby counteracts the need of, in a short duration, alternating
from heating to cooling, and vice versa. There are currently approximately 320
installed Ecopilots. For more information about the product and our customers,
please logon to ecopilot.com
Project
property Kuggen, Lindholmen Göteborg – independent evaluation of Ecopilot in a
modern office building
The building Kuggen is an office building
of 4,898 m2 divided on 5 floors and was put into operation in 2011.
From the start, even before Ecopilot, the building had good energy performance
and has been certified in accordance with the EU programme for energy-efficient
building, Green Building.
The evaluation was performed by an
independent party, CIT Energy Management AB, without links to the supplier of
Ecopilot. This evaluation covers six months (the time period September 2014 –
February 2015).
Conclusion
|
Without
Ecopilot Sep 2013 – Feb 2014 (MWh) |
With Ecopilot
Sep 2014 – Feb 2015 (MWh) |
Diff (MWh) |
Energy saving
(%) |
District heating consumption |
82.88 |
43.15 |
-39.73 |
-48 % |
Temperature corrected district heating consumption |
87.67 |
49.53 |
-38.14 |
-44 % |
Heat from heat pump |
90.58 |
44.49 |
-46.09 |
-51 % |
Total heat consumption |
173.46 |
87.64 |
-85.82 |
-49 % |
District cooling |
6.37 |
3.20 |
-3.17 |
-50% (5) |
Property electricity (incl. electricity for heat
pump) |
85.20 |
59.82 |
-25.38 |
-30 % |
Business electricity |
75.31 |
78.32 |
3.01 |
+4% |
(5) Does not cover the summer season with greatest
need of cooling and therefore it is difficult to draw conclusions about the
saving.
The conclusions which could be drawn are
that the requirements for the indoor
environment are fulfilled with Ecopilot. At Kabona we look forward to
contributing to property owners in Europe lowering their energy consumption to
the lowest level possible in a cost-efficient manner, with a payoff of
approximately 3–5 years.
Building candidate in the category

Low energy renovation